ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
36
Closer contacts: 30 VDC/AC, 0.4 A
PhotoMos-outputs
9.600 Baud, no parity, 8 Databit, 1 Stopbit,
cable length max. 1000 m
9.600 Baud, no parity, 8 Databit, 1 Stopbit,
cable length max. 3 m
Modbus with ASCII or RTU-protocol
Interface
Protocol
RS232
RS485
0/4-20 mA / burden
≤
500 Ohm, 0-10 VDC / burden
≥
10 kOhm, 16 bit
Analog output
100-240 VAC 50/60 Hz, DC ±10% (max. 15 VA)
Power supply
250 VAC / 5 AAC; 30 VDC / 5 ADC
30 x 10
5
with 5 AAC, 5 ADC ohm resistive burden
10 x 10
6
mechanically
Division according to DIN EN 50178 /
Characteristics according to DIN EN 60255
Output
Switching outputs
Relay with change-over contact
Switching cycles
EEPROM
Ambient conditions
≥
100 years / 25°C
Data life
According to low voltage directive 2006/95/EG
EN 61010; EN 60664-1
Safety standard
Conformity according to directive 2004/108/EG
CE-sign
EN 61326, EN 55011
EMV
relative humidity 0-80% on years average without dew
Wheatering resistance
-20…80°C
Storing temperature
0…50°C
Working temperature
Memory
34
10. Technical data