5. Setting up the device
27
The same applies for
Al2
to
al8
.
Switching-off delay,
toF-1:
Default:
000
For limit value 1 one can preset a delayed switching-off of 0-100 seconds.
Switching-on delay,
ton-1:
Default:
000
For limit value 1 one can preset a delayed switching-on of 0-100 seconds.
Function for threshold value undercut / exceedance,
Fu-1:
Default:
high
A limit value undercut is selected with
Louu
(for LOW = lower limit value), a limit value
exceedance with
High
(for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level
of 100 and allocated with function
High
, an alarm is activated by reaching of the threshold level.
If the threshold value was allocated to
Low,
an alarm will be activated by undercutting the
threshold value, as long as the hysteresis is zero.
Hysteresis for threshold values,
HY-1:
Default:
00000
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
Threshold values / limit values,
LI-1:
Default:
2000
The limit value defines the threshold, that activates/deactivates an alarm.
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group level
„–Al1–“
.
Parameterisation level
Menu level