12. Error elimination
12. Error elimination
6.
5.
4.
3.
2.
1.
• If you are not sure that the device has been
parameterised before, then follow the steps as
written in
chapter 6
and set it back to its delivery
status.
The device does not react as
expected.
• Please contact the manufacturer if errors of this
kind occur.
Err1
lights up in the 7-segment display
• Programming lock is activated
• Enter correct code
Program numbers for parameterising
of the input are not accessible.
• The unit has found an error in the configuration
memory. Perform a reset on the default values
and reconfigure the unit according to your
application.
The word
HELP
lights up in the
7-segment display.
• The input has a very low measurement, check
the measuring circuit.
• With a selected input with a low voltage signal,
it is only connected on one side or the input is
open.
• Not all of the activated setpoints are
parameterised. Check if the relevant
parameters are adjusted correctly.
The unit permanently shows
underflow.
• The input has a very high measurement, check
the measuring circuit.
• With a selected input with a low voltage signal,
it is only connected on one side or the input is
open.
• Not all of the activated setpoints are
parameterised. Check if the relevant
parameters are adjusted correctly.
The unit permanently indicates
overflow.
Measures