5. Setting up the device
14
Input variable of process value,
SIG.in
:
Default:
a.meas
With this parameter, the device can be controlled via the analog input signals
a.meas
= 10 VAC,
50 VAC respectively 1.5 AAC or via the digital signals of the interface
M.bus
= RS232/RS485
(Modbus protocol). With
[P]
the selection is confirmed and the device changes into menu level.
Display overflow,
dI.OUE:
Default:
99999
With this function the display overflow (
_ _ _ _ _
) can be defined on a definite value.
Back to menu group level,
rEt:
With
[P]
the selection is confirmed and the device changes into menu group level
„–INP–“
.
Parameterisation level
Menu level
5.4.2. General device parameters
Display time,
DISEC:
Default:
01.0
The display is set up with
[
▲
] [
▼
]
. Thereby it switches up to 1 second in increments of 0.1
seconds and up to 10.0 seconds in increments of 1.0. With
[P]
the selection is confirmed and
the device changes into menu level.
Parameterisation level
Menu level
Menu group level
Menu level
then