Installation of the drive connection
32
If you have a dual twisted pair cable, connect both wires of the second twisted pair to
ground.
The shields of all RS-485 network cables should be connected together. They
should be connected to only one device, for example the last drive of the network.
SREA-01
B+
A-
COM
X1 RS-485
SHLD
DG
B
A
SHLD
DG
B
A
SHLD
DG
B
A
…
Terminating resistor
Drive 1
Drive 2
Drive N
Terminating resistor
120 ohm
120 ohm