Quick start-up guide
19
Quick start-up guide
Mechanical installation
Mount the module to a DIN rail.
Connecting power and network
Connect
9–28 V AC/DC
to Vin+ and Vin- terminals. The power requirement of
SREA-01 is 2 W.
Connect an Ethernet cable directly to the unit for start up. You can use a network
after you have configured the unit.
Connecting drive(s)
With single drive, eg, ACS350, ACH550 or ACS550, use the supplied RJ45 cable.
Connect the RJ45 plug of the cable to the panel port of the drive and the other end to
the RS-232 terminal of SREA-01. Connect the wires according to the following table:
If you have multiple drives, use the RS-485 connection. Connect the A- channels of
the SREA-01 unit and the drives together, the B+ channels together and the COM
connector to the data ground connectors of the drives. Use 120 ohm terminating
resistors in the network.
Note:
Select the correct connection port under the Modbus setup page!
Connecting to SREA-01 over Ethernet
The default Ethernet configuration of the unit is:
IP address: 10.200.1.1
Subnet mask: 255.255.255.0
Username: admin
Password: admin
Terminal
Wire
RJ45 pin
RX (RS-232)
white-orange
1
TX (RS-232)
white-blue
3
COM
orange and blue
2, 6
Summary of Contents for SREA-01
Page 1: ...ABB Drives User s Manual Ethernet Adapter Module SREA 01 ...
Page 2: ......
Page 4: ......
Page 6: ...Safety instructions 6 ...
Page 16: ...Introduction 16 ...
Page 22: ...Quick start up guide 22 ...
Page 28: ...Electrical installation 28 ...
Page 90: ...Configuration pages 90 ...
Page 94: ...Fault tracing 94 ...
Page 104: ...Appendix C Creating custom device templates for unsupported devices 104 ...
Page 105: ......