These problems are listed in the
Output
view under the
Application Configuration
tab. Double-clicking the error or warning row navigates to the
MainApplication/
Page/Area
, where the problem was identified.
GUID-5779E523-6B82-4447-85E8-CAAA87141B6F V1 EN
Figure 49:
Application Configuration tool: validation on demand
5.1.9.3
Validation when writing to the protection relay
When writing the application configuration to the protection relay, an automatic
validation is performed. The validation is the same as the manually demanded
validation. Errors abort the writing.
5.1.10
Configuration load calculation
Connectivity package calculates an estimated application configuration load every
time it is saved in the Application Configuration tool or written to IED. This
functionality prevents too complex configurations from being used and possibly
risking IED protection functionality.
Calculation results are divided into three different sections which are OK, Warning
and Error. If the calculation result is 105% or more, the configuration is too large for
the IED to handle and PCM600 prevents writing the configuration to the IED. If the
configuration load is more than 100%, PCM600 gives a warning not to add
Section 5
1MRS757810 C
Protection and control engineering