GUID-3CA305F5-BDC0-4434-BB30-F9E0C2D0ECCA V1 EN
Figure 71:
Graphical Display Editor: drawing a line between symbols
6.1.2
Bay configuration engineering
A view with a single-line diagram and measurements contains active living objects.
The object values are updated by the protection relay periodically (measurement) or
in case of an event.
Once the symbols are placed on the HMI page, they must be linked to the
corresponding function block in the application configuration, which protects or
controls the object that the symbol on the HMI page represents.
6.1.2.1
Linking process objects
To describe a process object within an IED, it needs to be established in the application
configuration, configured when given the parameters by the Parameter Setting tool
and linked to be displayed in the HMI.
Three tools are involved in the described steps.
•
Application Configuration tool for programming the application function block
for the apparatus and measurements
•
Parameter Setting tool for adapting the settings and configuration parameters of
the application function block
•
Graphical Display Editor for establishing the link to update the selected data
attribute in the HMI of the application function block
Section 6
1MRS757810 C
LHMI engineering
100
REC615 and RER615
Engineering Manual