6.
Place measurements when needed.
7.
Edit the name, unit and the number of the measurements' decimals.
8.
Select each object that has a dynamic link and make the link to the corresponding
process object.
9.
Check that the correct function block is selected.
Function blocks of the same type can have different instance numbers.
GUID-CC72C442-0381-4FCD-B25A-C138CD48FCD2 V2 EN
Figure 74:
Graphical Display Editor: establishing a dynamic object link
10. Ensure that all links are done.
11. Save the complete picture.
12. Write to the IED.
13. Validate the single-line diagram on the protection relay.
6.2
Template export and import
The single-line diagram templates enable the reuse of the single-line diagram created
in the Graphical Display Editor tool. The single-line diagram can be exported as a
template and the same template can be imported to another IED. The file extension of
the single-line diagram template file is .psld.
6.2.1
Exporting a template
1.
Create a single-line diagram in the
Graphical Display Editor
tool.
2.
On the menu bar, point to
Graphical Display Editor
and select
Export Display
Pages as a Template
, or on the
File
menu, point to
Display Editor Template
and click
Export
.
3.
Once the display page is selected, click
Export
.
The
File save
dialog box appears.
4.
Browse the location to export the template and provide the file name.
1MRS757810 C
Section 6
LHMI engineering
REC615 and RER615
103
Engineering Manual