manager while the .pcmi files are meant for sharing the IED instances
between different PCM600 users enabling quick import/export
directly from the plant structure context menu.
IEC 61850 Edition 1 and Edition 2 IEDs cannot be used
simultaneously in the same PCM600 project. The first inserted IED
determines the IEC 61850 version for the whole project.
4.3.1
Inserting an IED in online mode
To set up an IED online, the protection relay must be connected to PCM600.
When the protection relay is already connected to PCM600, PCM600 can read the
order number directly from the relay. It is possible to read the full configuration from
the relay by using the
Read from IED
function.
1.
In the
Plant Structure
view, right-click the bay, point to
New
, point to the relay
application area such as
Motor Protection IEDs
and select the protection relay
type to be inserted.
Alternatively, drag an IED from the
Object Types
view to the
bay level.
Section 4
1MRS757810 C
Setting up a project
42
REC615 and RER615
Engineering Manual