5.
Check the default settings in the
SCL Import
view and change the settings if
they are not suitable.
The default settings in the
SCL Import
dialog should be correct in most cases.
6.
Click
Import
to import the SCD file.
7.
Check the IP address on the IEC 61850 subnetwork and change it if needed.
When the SCD file is directly exported from PCM600, it uses the IP address of
the PCM600 computer, not the COM600S.
The communication towards the protection relays is now ready. For information on
how to finalize the single-line diagram and enable parameter setting through
COM600S HMI, see COM600S documentation.
4.6
Using the Web HMI
WHMI is disabled by default, and has to be activated in the protection relay
configuration. As secure communication is enabled by default, the WHMI must be
accessed from a Web browser using the HTTPS protocol.
1.
To enable the WHMI, select
Main menu/Configuration/HMI/Web HMI
mode
via the LHMI.
2.
Reboot the relay for the change to take effect.
3.
Log in with the proper user rights to use the WHMI.
To establish a remote WHMI connection to the protection relay,
contact the network administrator to check the company rules for IP
and remote connections.
Disable the Web browser proxy settings or make an exception to the
proxy rules to allow the protection relay's WHMI connection, for
example, by including the relay's IP address in
Internet Options/
Connections/LAN Settings/Advanced/Exceptions
.
For more information on the WHMI, see the operation manual.
4.7
Managing IED users
IED user authorization is disabled by default. IED user passwords can be changed in
LHMI, WHMI and using the IED Users tool in PCM600.
1MRS757810 C
Section 4
Setting up a project
REC615 and RER615
61
Engineering Manual