see the application manuals. The product also includes the standard configuration
specific default single-line diagram.
The standard configuration software consists of connections between an application's
functions developed according to the needs of a particular functional application. The
inputs and outputs are similarly assigned to a default set of connections such as
position indication and Master trip. The alarm LEDs are assigned to default
connections based on the order number.
Current and voltage channels for protection and measurement
functions are fixed as a part of standard configuration and cannot be
reassigned with Signal Matrix or Application Configuration in
PCM600.
The single-line diagram consists of an application-specific general arrangement of a
single-line diagram that includes position indications and the selection of controllable
objects and measurements.
The content of the standard configuration depends on the intended functional
application. The standard configurations also have selectable software options, which
are selected when ordering the protection relay. Some of the software options are
related to the protection relay hardware.
The standard configurations can be used as is, but they can also be modified by using
the PCM600. The standard configuration itself can be modified or extended by using
the Application Configuration tool, the Signal Matrix tool and the communication
configuration tools. The single-line diagram can also be modified with Graphical
Display Editor.
All functions and application logic included in a standard configuration of the
protection relay can be in use at the same time.
However, by removing unused function blocks from the configuration with the
Application Configuration in PCM600, more resources in the protection relay become
available for other purposes.
•
More advanced user application logic with Application Configuration
•
Extensive use of GOOSE sending and receiving
•
Increasing the amount of data reported for IEC 61850 clients