ChannelMode
defines how an IED discards the LDCM information when one of the
IEDs in the system is out of service: it can either be done on the IED out of service by
setting all local LDCMs to channel mode
OutOfService
or at the remote end by setting
the corresponding LDCM to channel mode
Blocked
. If
OutOfService
is selected, the
IED should have active communication to the remote end during the whole
maintenance process, that is, no restart or removal of the fibre can be done.
This setting does not apply to two-end communication.
Blocked
IED does not use data from the LDCM
OutOfService
IED informs the remote end that it is out of service
TerminalNo
is used to assign a unique address to each LDCM in all current differential
IEDs. Up to 256 LDCMs can be assigned a unique number. For example, in a local
IED with two LDCMs:
•
LDCM for slot 305: set
TerminalNo
to 1 and
RemoteTermNo
to 2
•
LDCM for slot 306: set
TerminalNo
to 3 and
RemoteTermNo
to 4
In multiterminal current differential applications,with 4 LDCMs in each IED, up to 20
unique addresses must be set.
A unique address is necessary to give high security against incorrect
addressing in the communication system. If the same number is used
for
TerminalNo
in some of the LDCMs, a loop-back test in the
communication system can give an incorrect trip.
RemoteTermNo
is used to assign a number to each related LDCM in the remote IED.
For each LDCM,
RemoteTermNo
is set to a different value than
TerminalNo
, but equal
to the
TerminalNo
of the remote end LDCM. In the remote IED,
TerminalNo
and
RemoteTermNo
are reversed as follows:
•
LDCM for slot 305: set
TerminalNo
to 2 and
RemoteTermNo
to 1
•
LDCM for slot 306: set
TerminalNo
to 4 and
RemoteTermNo
to 3
The redundant channel is always configured to the lower position, for
example:
•
Slot 305: main channel
•
Slot 306: redundant channel
Section 21
1MRK 502 071-UUS A
Remote communication
764
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...