Setting of zone 1
GUID-69E8535D-F3E2-483D-8463-089063712C67 v2
A voltage reversal can cause an artificial internal fault (voltage zero) on faulty line as
well as on the adjacent lines. This artificial fault always have a resistive component,
this is however small and can mostly not be used to prevent tripping of a healthy
adjacent line.
An independent tripping zone 1 facing a bus which can be exposed to voltage reversal
have to be set with reduced reach with respect to this false fault. When the fault can
move and pass the bus, the zone 1 in this station must be blocked. Protection further
out in the net must be set with respect to this apparent fault as the protection at the bus.
Different settings of the reach for the zone (ZMFCPDIS, 21) characteristic in forward
and reverse direction makes it possible to optimize the settings in order to maximize
dependability and security for independent zone1.
Due to the sub-harmonic oscillation swinging caused by the series capacitor at fault
conditions the reach of the under-reaching zone 1 must be further reduced. Zone 1 can
only be set with a percentage reach to the artificial fault according to the curve in
99000202.vsd
p
100
80
60
40
20
0
100 %
80
60
40
20
C
%
IEC99000202 V1 EN-US
Figure 130:
Reduced reach due to the expected sub-harmonic oscillations at
different degrees of compensation
c
l
X
c degree of compensation
X
æ
ö
=
ç
÷
ç
÷
è
ø
EQUATION1894 V1 EN-US
(Equation 123)
Section 8
1MRK 502 071-UUS A
Impedance protection
268
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...