Stator gain should be set to the VT/DT rating. That voltage is dependent on the VT/DT
ratio and the highest possible voltage at neutral point. Gain factor (VmaxEF) shall be
selected to correspond to this voltage which shall be at least the same as VT/DT value
in table below.
Table 33:
Stator gain
UmaxEF [V]
Note
240
200
160
Default value
up to 120
8.8.3.2
Connecting and setting voltage inputs
GUID-18C586FE-4BFD-4037-A0F2-94696557FF33 v2
The SIM module of REX060 has two analog output channels that shall be connected to
two voltage input channels of the IED.
If both stator and rotor protection are used, there are two possible methods to perform
the connection.
1. The recommended connection requires four analog channels of the IED: two IED
voltage channels are used for the measured quantities for STTIPHIZ; two more
IED voltage channels are used for the measured quantities for ROTIPHIZ.
1MRK 502 071-UUS A
Section 8
Impedance protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
327
Application manual