Considering the safety margins mentioned previously, the minimum setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION288 V3 EN-US
(Equation 183)
The IED setting value
IN>>
is given in percent of the primary base current value,
IBase. The value for
IN>>
is given by the formula:
(
) 100
s
IN
I
IBase
IECEQUATION17003 V1 EN-US
(Equation 184)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (
IBase
).
Operation
: set the protection to
Enabled
or
Disabled
.
Pickup
: Set operate current in % of
IB
.
IN>>Max
and
IN>>Min
should only be changed if remote setting of operation current
level,
IN>>
, is used. The limits are used for decreasing the used range of the
IN>>
setting. If
IN>>
is set outside
IN>>Max
and
IN>>Min
, the closest of the limits to
IN>>
is used by the function. If
IN>>Max
is smaller than
IN>>Min
, the limits are
swapped.
MultPU
: The set operate current can be changed by activation of the binary input
MULTPU to the set factor
MultPU
.
9.4
Directional residual overcurrent protection, four steps
EF4PTOC (51N/67N)
IP14509-1 v8
9.4.1
Identification
M14881-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
Section 9
1MRK 502 071-UUS A
Current protection
362
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...