when they are set to 0=FALSE.
15.3.2
Interlocking for line bay ABC_LINE (3)
IP14139-1 v2
15.3.2.1
Application
M13561-3 v8
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure
. The
function can also be used for a double busbar arrangement without transfer busbar or a
single busbar arrangement with/without transfer busbar.
189
289
189G
289G
989
989G
WA1 (A)
WA2 (B)
WA7 (C)
789
en04000478_ansi.vsd
152
ANSI04000478 V1 EN-US
Figure 242:
Switchyard layout ABC_LINE (3)
M13560-4 v5
The signals from other bays connected to the module ABC_LINE (3) are described
below.
15.3.2.2
Signals from bypass busbar
M13560-6 v5
To derive the signals:
Signal
BB7_D_OP
All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D
The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB
No transmission error from any bay containing disconnectors on bypass busbar
WA7
1MRK 502 071-UUS A
Section 15
Control
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
561
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...