Operation
:
Disabled
/
Enabled
EnaAcc
:
Disabled
/
Enabled
is used to switch the accumulation of energy on and off.
tEnergy
: Time interval when energy is measured.
tEnergyOnPls
: gives the pulse length ON time of the pulse. It should be at least
100
ms
when connected to the Pulse counter function block. Typical value can be
100
ms.
tEnergyOffPls
: gives the OFF time between pulses. Typical value can be
100
ms.
EAFAccPlsQty
and
EARAccPlsQty
: gives the MWh value in each pulse. It should be
selected together with the setting of the Pulse counter (PCGGIO) settings to give the
correct total pulse value.
ERFAccPlsQty
and
ERVAccPlsQty
: gives the MVArh value in each pulse. It should be
selected together with the setting of the Pulse counter (PCGGIO) settings to give the
correct total pulse value.
For the advanced user there are a number of settings for direction, zero clamping, max
limit, and so on. Normally, the default values are suitable for these parameters.
Section 18
1MRK 502 071-UUS A
Metering
734
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual