15.2.1.2
Switch controller SCSWI
M16596-3 v5
SCSWI may handle and operate on one three-phase device or three one-phase
switching devices.
After the selection of an apparatus and before the execution, the switch controller
performs the following checks and actions:
•
A request initiates to reserve other bays to prevent simultaneous operation.
•
Actual position inputs for interlocking information are read and evaluated if the
operation is permitted.
•
The synchronism check/synchronizing conditions are read and checked, and
performs operation upon positive response.
•
The blocking conditions are evaluated
•
The position indications are evaluated according to given command and its
requested direction (open or closed).
The command sequence is supervised regarding the time between:
•
Select and execute.
•
Select and until the reservation is granted.
•
Execute and the final end position of the apparatus.
•
Execute and valid close conditions from the synchronism check.
At error the command sequence is cancelled.
In the case when there are three one-phase switches (SXCBR) connected to the switch
controller function, the switch controller will "merge" the position of the three switches
to the resulting three-phase position. In case of a pole discrepancy situation, that is, the
positions of the one-phase switches are not equal for a time longer than a settable time;
an error signal will be given.
The switch controller is not dependent on the type of switching device SXCBR or
SXSWI. The switch controller represents the content of the SCSWI logical node
(according to IEC 61850) with mandatory functionality.
15.2.1.3
Switches SXCBR/SXSWI
M16602-3 v6
Switches are functions used to close and interrupt an ac power circuit under normal
conditions, or to interrupt the circuit under fault, or emergency conditions. The
intention with these functions is to represent the lowest level of a power-switching
device with or without short circuit breaking capability, for example, circuit breakers,
disconnectors, grounding switches etc.
Section 15
1MRK 502 071-UUS A
Control
546
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...