![ABB FEX300 Operating Instruction Download Page 93](http://html1.mh-extra.com/html/abb/fex300/fex300_operating-instruction_3745924093.webp)
Parameterization
OI/FEX300/FEX500-EN FEX300,
FEX500
93
7.4.2 Menu:
Device
Info
Important (Notice)
This menu is used only to display the device parameters. The parameters are displayed
independently of the configured access level, but cannot be changed.
Menu / Parameter
Value range
Description
Device Info
Sensor
Select the "Sensor" submenu.
Acquisition
Select the "Acquisition" submenu.
Analog Range
Select the "Analog Range" submenu.
Transmitter
Select the "Transmitter" submenu.
Device Info /
Sensor
Sensor Type
-
Type of flowmeter sensor (ProcessMaster 300 / 500,
HygienicMaster 300 / 500).
Important (Notice)
When commissioning the device, make sure that
the transmitter is assigned to the sensor
correctly. It is not possible to operate a flowmeter
sensor of the 300 series with a transmitter of the
500 series.
Sensor Model
-
Indication of model number (e.g., FEP315)
Sensor Size
-
Size of sensor.
QmaxDN
-
This value is the maximum flow at a velocity of 10
m/s.
The value is set automatically via the selected
flowmeter size.
Qmax
-
Set flow range end value for flow range 1.
Factory setting: Flow range 1 activated.
Qmax 2
-
Set flow range end value for flow range 2.
Factory setting: Flow range 2 deactivated.
Important (Notice)
The switchover between the two measuring
ranges is done via the digital input or via the
menu "Config. Device / Sensor / 2 flow ranges“
Span Ss
-
Calibration value for the sensor (span)
Zero Sz
-
Calibration value for the sensor (zero)
italics
= Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.
Summary of Contents for FEX300
Page 169: ...Appendix OI FEX300 FEX500 EN FEX300 FEX500 169...
Page 170: ...Appendix 170 FEX300 FEX500 OI FEX300 FEX500 EN...
Page 175: ......