Parameterization
OI/FEX300/FEX500-EN FEX300,
FEX500
91
Menu / Parameter
Value range
Description
Easy Setup (continued)
"Easy Setup" Menu
Pulse Width
0.1 ... 2000 ms
Select the pulse width for the digital output. The pulse
factor and pulse width are interdependent and are
calculated dynamically.
Damping
0.02 ... 60 s
Select the damping.
The value set here relates to 1
Τ
(Tau).
The value refers to the response time for a step
flowrate change. It affects the instantaneous value in
the display and at the current output.
Default setting: 1 second
Iout at Alarm
Low, High
Status of the current output during an error.
The “low” or “high” status is set in the subsequent
menu.
Default setting: "High".
Low Alarm Value
3.5 ... 3.6 mA
Current for Low Alarm.
Default setting: 3.5 mA
High Alarm Value
21 ... 23 mA
Current for High Alarm.
Default setting: 21.8 mA
System Zero
Select the "System Zero" submenu.
italics
= Parameter can only be viewed at the "Advanced" password level.
1) Parameter / menu only available for FEP500 / FEH500.