Commissioning
OI/FEX300/FEX500-EN FEX300,
FEX500
69
Instructions on using the Qmax menu (flow range end value)
The device is factory calibrated to the flow range end value Qmax
DN
, unless other customer
information is available. The ideal flow range end values are approximately 2-3 m/s (0.2 ... 0.3 x
Q
max
DN).
The smallest and largest possible flow range end values are shown in the table in chapter
"
".
Information regarding factory settings for further parameters (unless customer has
requested a specific parameterization)
Possible parameter settings Factory setting
Qmax
Depending on the size (see
table)
QmaxDN (see table)
Sensor TAG
Alphanumeric, max.
20 characters
None
Sensor Location TAG
Alphanumeric, max.
20 characters
None
Q (Flowrate) Unit
l/s; l/min; l/h; ml/s; ml/min;
m3/s; m3/min; m3/h; m3/d;
hl/h; g/s; g/min; g/h; kg/s;
kg/min; kg/h; kg/d; t/min; t/h;
t/d
l/min
Totalizer/Pulse Unit
m3; l; ml; hl; g; kg; t
l
Pulses per Unit
1
Pulse Width
0,1 ... 2,000 ms
100 ms
Damping ( 1 Tau)
0,02 ... 60 sec.
1
DO1 Alarm Config
Pulse F/Pulse R, Pulse F,
General Alarm, Min. Flowrate
Alarm, Max. Flowrate Alarm,
Empty Pipe, TFE
Only available for
FEP500 / FEH500 are:
Gas Bubble, Conductivity,
Coating, Sensor Temp
Pulse F/Pulse R
DO1 Action
Active, Passive
Passive
DO2 Alarm Config
F/R Signal, Pulse R, General
Alarm, Min. Flowrate Alarm,
Max. Flowrate Alarm, Empty
Pipe, TFE
Only available for
FEP500 / FEH500 are:
Gas Bubble, Conductivity,
Coating, Sensor Temp
F/R Signal