![ABB FEX300 Operating Instruction Download Page 112](http://html1.mh-extra.com/html/abb/fex300/fex300_operating-instruction_3745924112.webp)
Parameterization
112 FEX300,
FEX500
OI/FEX300/FEX500-EN
Menu / Parameter
Value range
Description
Communication /
Service Port
Max Baud Rate
2400, 4800, 9600, 19200,
38400
Set the transmission rate (baud rate) for the infrared
service port.
HART Access
On / Off
Activate / deactivate the infrared service port
Communication /
PROFIBUS
The menu is displayed only for devices with
PROFIBUS PA.
PA Addr. (-BUS-)
0 ... 126
The "PROFIBUS" is displayed only if this option has
been ordered for the device. Display of the slave
address.
Factory setting: 126
Information for the DIP switches:
• DIP switches 1 to 7 define the PROFIBUS
address,
• DIP switch 8 defines the address mode:
• DIP switch 8 = Off = Addressing via bus or keypad
using the menus for the device. The message "-
BUS-" is displayed.
• DIP switch 8 = On = Addressing via DIP switches
1-7; the message “(HW Switch)“ is displayed.
The address switch setting is only adopted when
the device is restarted, not during running
operation.
Factory setting for DIP switch 8: Off
For further information read and observe chapter 6.3
“Commissioning PROFIBUS PA units”.
Ident Nr. Selector
0x9700, 0x9740, 0x3430
Select the ID No. Selector. The parameter can be
changed only when cyclic communication is stopped
(Comm State = OFF).
Default setting: 0x3430
Comm State
Offline, Operate, Clear, Stop
Display of the communication status.
• Offline:
BUS communication is deactivated.
• Operate:
Cyclic communication is running.
• Clear:
Device is being initialized.
• Stop:
Cyclic communication is stopped, BUS
communication remains active.
AI1-Q Flowrate
Display only
Current flow in the selected unit from the Transducer
Block Flow, including status.