7.5
Alarm Simulation
In the "Process Alarm / Alarm Simulation" menu a variety of alarms can be simulated.
Parameter
Description
Process Alarm
... / Alarm Simulation
Off
Alarm Simulation switched off.
0-Sim.CurrentOut
Simulate current output
1-Sim.Logic on DO1
Switch on/off contact output (terminals 51, 52)
2-Sim.Pulse on DO1
Simulate pulse output (terminal 51/52)
3-Sim.Logic on DO2
Switch on/off contact output (terminals 41, 42)
4-Sim.Pulse on DO2
Simulate pulse output (terminal 51/52)
5-Min Alarm Flowrate
Simulate flowrate min. alarm
6-Max Alarm Flowrate
Simulate flowrate max. alarm
7-Flowrate >103%
Simulate flowrate > 103 % as alarm
8-Flow Simulation
Run flowrate simulation
9-Calbration Mode
Run transmitter alarm on simulator
10-Flowrate to Zero
Simulate external output switch-off
11-Totalizer Stop
Simulate external totalizer stop
12-Tot.Display<1600h
Simulate display value <1600 h for Qmax.
13-Totalizer Reset
Simulate external totalizer reset
14-Err.Sensor-Comms
Simulate distorted communication to SensorMemory.
15-HART Address <> 0
Simulate HART Multiplex mode
16-FRAM-Com Fail
Simulate FRAM error in the transmitter
17-No Sensor
Simulate error "No communication to SensorMemory"
18-Sim.Digital Input
Simulate digital input "ON/OFF"
19-ADC saturated
Simulate "AD converter override" error
20-Error Coil circ
Simulate error in coil loop
21-Coil Resistor
Simulate "Coil resistance out of limits" error
22-Driver Err Uref=0
Simulate "Reference voltage = 0" error
23-El.Noise too High
Simulate "Noise signal too high" error
24-DC to High
Simulate "DC too high, several NV resets" error
25-Empty Pipe
Simulate "Empty pipe" error
26-Short Circuit
Simulate "Electrode voltage out of limits" error
27-NV Corrupt
Simulate "NV Corrupt" error
29-Electrode Imp.
Simulate "Electrode impedance out of limits" error