Commissioning
70 FEX300,
FEX500
OI/FEX300/FEX500-EN
Possible parameter settings Factory setting
Digital Input Setup
No Function, Totalizer
Reset(All), Flowrate to Zero,
System Zero Adjust, Totalizer
Stop(All), Only available for
FEP500 / FEH500 are:
Dual Range, Start/Stop
Batching
Flowrate to Zero
Current Output
4 … 20 mA, 4 … 12 … 20 mA 4 - 20 mA
Iout at Alarm
High Alarm, can be set to
21 … 23 mA or
Low Alarm, can be set to
3.5 … 3.6 mA
High Alarm, 21.8 mA
For details refer to Section
9.2.
Iout at Flow >103%
Off (no signaling, current
output holds 20.5 mA), High
Alarm, Low Alarm
Off
Low Flow Cut Off
0 … 10 %
1 %
Empty Pipe Detector
On / Off
Off
TFE Detector
On / Off
Off
For PROFIBUS PA version
Possible parameter settings Factory setting
PA Addr. (BUS)
0 … 126
126
ID Nr Selector
0x9700, 0x9740, 0x3430
0x3430