![ABB FEX300 Operating Instruction Download Page 145](http://html1.mh-extra.com/html/abb/fex300/fex300_operating-instruction_3745924145.webp)
Error
messages
OI/FEX300/FEX500-EN FEX300,
FEX500
145
Error no.
range
Text on the LCD
display
Current
output
behavior
Digital output
behavior
Pulse
output
behavior
Display
Error
maskable?
C154.018
Configuration
Simulation
Digital In
Switch off
Simulation Mode
Current value
No response
Current value
Current
value
Mask group
C149.021
Sensor
Coil resistor
out of limits
Check wiring
Contact
ABB Service
Current value
No response
Current value
Current
value
Mask group
S148.025
Operation
Empty Pipe
Check Pipe
Programmed
alarm
Programmed alarm
0 Hz
0%
Mask single
alarm
S149.021
Operation
Gas Bubble Alarm
No response
No response
No response
No
response
Mask group
S146.043
Operation
Partially
filled pipe(TFE)
Check Pipe
Or adjust
Detector
Current value
Programmed alarm
Current value
Current
value
Mask group
S144.033
Operation
Electrode
Coating Alarm
Programmed
alarm
Programmed alarm
Current value
Current
value
Mask group
S143.042
Operation
Conductivity Alarm
Current value
Programmed alarm
Current value
Current
value
Mask group
S142.041
Operation
Sensor and or Housing
Temperature to high
Current value
Programmed alarm
Current value
Current
value
Mask group
S141.046
Operation
Flowrate >103%
Check Flowrate
Check Range
Setting
Current value
Programmed alarm
Current value
Current
value
Mask group
S140.007
Operation
Max Alarm
Flowrate
Programmed
alarm
Collective Alarm
Current value
Current
value
Mask single
alarm
S136.006
Operation
Min Alarm
Flowrate
Current value
Programmed alarm
Current value
Current
value
Mask single
alarm
S132.05
Operation
Coil resistor
out of limits
Check wiring
Contact
ABB Service
Current value
Programmed alarm
Current value
Current
value
Mask single
alarm
S124.029
Operation
Electr.Impedance
too high
Coating?
Conductivity?
Empty Pipe?
Current value
No response
Current value
Current
value
Mask group
S122.026
Operation
Short-ciruit E1
E2 with shield.
Current value
No response
Current value
Current
value
Mask group
Summary of Contents for FEX300
Page 169: ...Appendix OI FEX300 FEX500 EN FEX300 FEX500 169...
Page 170: ...Appendix 170 FEX300 FEX500 OI FEX300 FEX500 EN...
Page 175: ......