The following table contains the list of logical nodes implemented in the device:
L: System Logical Nodes
LPHD (physical device information)
LLN0 (logical node zero)
G: Logical Nodes for Generic References
GGIO (generic process I/O)
S: Logical Nodes for Sensors and Monitoring
SIML (insulation medium supervision [liquid])
SIML–Insulation medium supervision (liquid)
The IEC 61850-7-4 ed.1 SIML node was extended with data objects defined in technical report
IEC 61850-90-4, ed.1.
SIML
DO Name
CDC
Explanation
M/O/C/E
Lnname
Shall be inherited from Logical-node Class (see ieC 61850-7-2)
Data Objects
Common Logical Node Information
Mod
inC
Mode
M
Beh
inS
Behavior
M
Health
inS
Health
M
namplt
LpL
name plate
M
Measured Values
H2O
MV
Relative saturation of moisture in insulating liquid (in %)
O
H2OTmp
MV
Temperature of insulating liquid at point of H₂O measurement
O
H2
MV
Measurement of hydrogen (in ppm)
O
H2Oppm
MV
Measurement of moisture (in ppm)
e
H2RoC
MV
Hydrogen rate of change (RoC in ppm/day)
e
MstRoC
MV
Moisture rate of change (RoC in ppm/day)
e
CH4
MV
Measurement of methane (in ppm)
e
CH4ROC
MV
Methane rate of change (RoC in ppm/day)
e
CO2
MV
Measurement of carbon dioxide (in ppm)
e
CO2ROC
MV
Carbon dioxide rate of change (RoC in ppm/day)
e
CO
MV
Measurement of carbon monoxide (in ppm)
e
COROC
MV
Carbon monoxide rate of change (RoC in ppm/day)
e
C2H2
MV
Measurement of acetylene (in ppm)
e
C2H2ROC
MV
Acetylene rate of change (RoC in ppm/day)
e
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......