Modifying 4–20 mA output values
Sometimes, when performing maintenance or troubleshooting tasks, you need to modify certain
electric output currents.
To do so:
1
Click
I/O diagnostics>Outputs 4-20mA
from the
Maintenance
page. The
Outputs 4-20mA
page
appears, indicating the various current outputs.
2
Modify the indicated current outputs as required by your troubleshooting or maintenance task.
—
Figure 66
4–20mA outputs page
3
Click
Apply
. The current outputs are modified as indicated.
NOTICE
The CoreSense M10 is designed to counteract undue external influences by resetting
current outputs to a preferred state every 30 seconds. If your testing of the current
outputs exceeds 30 seconds, click
Refresh
to obtain the latest relay states before
continuing on.