B60
User Guide
Pointmap1 2 3
4
5
Analog input
Binary input
Name
Point index
Unit
Name
Point index
4–20 mA
6
input 1
10
mA
n/a
n/a
4–20 mA input 2
11
mA
n/a
n/a
4–20 mA input 3
12
mA
n/a
n/a
4–20 mA input 4
13
mA
n/a
n/a
CH4
23
ppm
CH4_Lev_Warn
15
CH4_Roc_day
24
ppm/day
CH4_Lev_Crit
16
Reserved
25
–
CH4_Roc_Warn
17
Reserved
26
–
CH4_Roc_Crit
18
CO2
27
ppm
CO2_Lev_Warn
19
CO2_Roc_day
28
ppm/day
CO2_Lev_Crit
20
Reserved
29
–
CO2_Roc_Warn
21
Reserved
30
–
CO2_Roc_Crit
22
CO
31
ppm
CO_Lev_Warn
23
CO_Roc_day
32
ppm/day
CO_Lev_Crit
24
Reserved
33
–
CO_Roc_Warn
25
Reserved
34
–
CO_Roc_Crit
26
C2H2
35
ppm
C2H2_Lev_Warn
27
C2H2_Roc_day
36
ppm/day
C2H2_Lev_Crit
28
Reserved
37
–
C2H2_Roc_Warn
29
Reserved
38
–
C2H2_Roc_Crit
30
C2H4
39
ppm
C2H4_Lev_Warn
31
C2H4_Roc_day
40
ppm/day
C2H4_Lev_Crit
32
Reserved
41
–
C2H4_Roc_Warn
33
Reserved
42
–
C2H4_Roc_Crit
34
C2H6
43
ppm
C2H6_Lev_Warn
35
C2H6_Roc_day
44
ppm/day
C2H6_Lev_Crit
36
1 Event class is None
2 For binary inputs, name for state when value is zero = off.
3 For binary inputs, name for state when value is one = on.
4 Rate-of-change (RoC) is calculated on a 24-hour time period.
5 For analog inputs, the multiplier is always 0.1 and the offset, 0
6 4–20 mA inputs' function is scaled by 100
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......