A ppendix e
Alternate fluids validation
Mineral Oil (IEEE Std C57.104-2019)
—
Table 2
Default dissolved gas concentration limits for Mineral Oil (µL/L [ppm])
Gaz
Warning threshold
Alarm threshold
Default state
Moisture (H₂O)
10
20
enabled
Hydrogen (H₂)
80
200
enabled
Methane (CH₄)
90
150
enabled
Acetylene (C₂H₂)
2
7
enabled
Ethylene (C₂H₄)
50
100
enabled
Ethane (C₂H₆)
90
175
enabled
Carbon monoxide (CO)
900
1100
enabled
Carbon dioxide (CO₂)
9000
12500
enabled
TDCG
n/a
n/a
Disabled
Propene (C₃H₆)
15
30
Disabled
Propane (C₃H₈)
n/a
n/a
Disabled
Synthetic Ester (IEEE Std C57.155-2014)
—
Table 3
Default dissolved gas concentration limits for Synthetic Ester (µL/L [ppm])
Gaz
Warning threshold
Alarm threshold
Default state
Moisture (H₂O)
400
600
enabled
Hydrogen (H₂)
64
88
enabled
Methane (CH₄)
104
144
enabled
Acetylene (C₂H₂)
13
42
enabled
Ethylene (C₂H₄)
150
230
enabled
Ethane (C₂H₆)
124
474
enabled
Carbon monoxide (CO)
1344
1541
enabled
Carbon dioxide (CO₂)
1300
1500
enabled
TDCG*
n/a
n/a
Disabled
Propene (C₃H₆)
25
50
enabled
Propane (C₃H₈)
75
150
enabled
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......