A ppendix C
IEC 61850
The CoreSense M10 implements an IEC 61850 MMS server over TCP/IP Ethernet that is compliant with
edition 1 of the IEC 61850 standard.
pixiT
protocol implementation extra information for Testing
MiCS
Model implementation Conformance Statement
piCS
protocol implementation Conformance Statement
TiCS
Technical issues implementation Conformance Statement
CoreSenseStrict.icd
iCd file which does not contain extended data attributes
CoreSenseextended.icd
iCd file which contains extended data attributes
For your convenience, selected information is available in this appendix.
PIXIT
PIXIT for Association Model
ID
ED
Description
Value/Clarification
As1
1
Maximum number of clients that can set-up an association
simultaneously
2
As2
1.2
TCp_KeepALiVe value. The recommended range is 1..20 s
5 seconds
As3
1,2
Lost connection detection time
5 sec (idle) + (5 sec * 5 retry) = 30
seconds
As4
-
Authentication is not supported yet
nA
As5
1,2
What association parameters are necessary for successful
association
Transport selector
Y
Session selector
Y
presentation selector
Y
Ap Title
n
Ae Qualifier
n
As6
1,2
if association parameters are necessary for association,
describe the correct values e.g.
Transport selector
00 01
Session selector
00 01
presentation selector
00 00 00 01
Ap Title
nA
Ae Qualifier
nA
As7
1,2
What is the maximum and minimum MMS pdU size
Max MMS pdU size
120000
bytes
Min MMS pdU size
1200 bytes
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......