![ABB CoreSense M10 User Manual Download Page 106](http://html.mh-extra.com/html/abb/coresense-m10/coresense-m10_user-manual_4370106.webp)
E102
User Guide
Natural Ester (IEEE Std C57.155-2014)
—
Table 4
Default dissolved gas concentration limits for Natural Ester (µL/L [ppm])
Gaz
Warning threshold
Alarm threshold
Default state
Moisture (H₂O)
200
300
enabled
Hydrogen (H₂)
112
171
enabled
Methane (CH₄)
20
41
enabled
Acetylene (C₂H₂)
1
3
enabled
Ethylene (C₂H₄)
18
36
enabled
Ethane (C₂H₆)
232
389
enabled
Carbon monoxide (CO)
161
462
enabled
Carbon dioxide (CO₂)
80
230
enabled
TDCG*
n/a
n/a
Disabled
Propene (C₃H₆)
10
20
enabled
Propane (C₃H₈)
20
40
enabled
Silicon Fluid(IEEE Std C57.146-2005)
—
Table 5
Default dissolved gas concentration limits for Silicon Fluid (µL/L [ppm])
Gaz
Warning threshold
Alarm threshold
Default state
Moisture (H₂O)
70
105
enabled
Hydrogen (H₂)
200
300
enabled
Methane (CH₄)
100
150
enabled
Acetylene (C₂H₂)
1
3
enabled
Ethylene (C₂H₄)
30
45
enabled
Ethane (C₂H₆)
30
45
enabled
Carbon monoxide (CO)
3000
4500
enabled
Carbon dioxide (CO₂)
30000
45000
enabled
TDCG*
n/a
n/a
Disabled
Propene (C₃H₆)
n/a
n/a
Disabled
Propane (C₃H₈)
n/a
n/a
Disabled
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......