Configuring communication protocols
19
4–20 mA output channels
In the CoreSense M10, 4–20 mA outputs can be defined for up to eight gas sensors (channels 1 to 8). All
channels can be configured the same way. In the following procedure, channel 1 is used as an example.
To configure the output for one gas sensor:
1
From the Publication settings page, click
o420
(for output 4–20; see Figure 18 on page 19).
On the page that appears, you can configure up to eight channels.
2
Under
Channel 1
, select the output that you want from the
Value
drop-down menu.
From the menu, you have access to the values of 10 gas sensors (fgs) and four channels.
The four channels correspond to the 4–20 mA inputs.
—
Figure 18
Selecting a channel value unit
3
Enter the appropriate values in ppm in the
4 mA value
and
20 mA value
fields. For more information
on the range of possible values, refer to the measurement specifications in the Installation Guide.
When you select a value in the Value drop-down list, default values appear in the
4 mA value
and
20 mA value
fields.
4
Repeat steps 2 and 3 for all required channels.
5
Scroll to the bottom of the page and click
Apply
. Values are set for the output channels that you
selected.
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......