A54
User Guide
Modbus parameters
NOTICE
Only read-only holding registers are supported in this implementation.
The Modbus slave ID is 1.
Register
Modbus
number
Parameter
Function
Datatype
DataRange
Reserved
0
not supported
1-10
Reserved
info
11-20
40011
Model number
ASCii string
21-30
40021
Serial number
ASCii string
31-40
40031
SW revision
ASCii string
41-50
40041
System id
ASCii string
51
40051
Manufacturing date
high byte =
month
low byte =
day
32-bit binary value
52
40052
Year
System status
53
40053
System status
see <Status>
table
16-bit binary map
see <Status>
table
54
40054
FGS status
internal error
signed 16-bit binary number
ABB service
dissolved gas and moisture
55
40055
Moisture status
16-bit binary map
see <Gas
status> table
56
40056
Moisture (aw)
scaled by
1000
signed 16-bit binary number
57
40057
Moisture (ppm)
signed 16-bit binary number
58
40058
Moisture RoC (ppm/day)
signed 16-bit binary number
59
40059
ReSeRVed–Moisture RoC
(ppm/week)
return 0
signed 16-bit binary number
60
40060
ReSeRVed–Moisture RoC
(ppm/month)
return 0
signed 16-bit binary number
61
40061
Hydrogen status
16-bit binary map
see <Gas
status> table
62
40062
Hydrogen (ppm)
signed 16-bit binary number
63
40063
Hydrogen RoC (ppm/day)
signed 16-bit binary number
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......