Setting up the analyzer
7
Activating the sensor head thermal pump
This step should have been performed during system installation and commissioning, so this is mostly
a reminder of this critical procedure.
The CoreSense M10 sensor head is delivered with its thermal pump turned off. For configuration
purposes, the sensor head
can be powered when it does not contain any transformer fluid.
However, its thermal pump must be turned off.
When installation is complete and the sensor head is
in contact with transformer fluid, make sure to activate the thermal pump.
NOTICE
The thermal pump will fail
within minutes
if operated in air.
To activate the thermal pump:
1
From the CoreSense M10 dashboard (see Figure 2 on page 3), click
Settings
. The Settings page
2
Click
Administration settings
and enter your password (for more information on passwords, see
“Changing passwords” on page 5).
3
Scroll down to the
Application settings
section and check the
Enable thermal pump
box.
When you check this box, a reminder appears, asking you to verify that the sensor head is properly
connected to the transformer (i.e., in contact with oil).
4
At the bottom of the page, click
Apply
to confirm activation of the thermal pump.
—
Figure 5
Activating the thermal pump
Summary of Contents for CoreSense M10
Page 1: ... USER GUIDE CoreSense M10 Multi gas monitoring system ...
Page 8: ...Page intentionally left blank ...
Page 18: ...Page intentionally left blank ...
Page 24: ...Page intentionally left blank ...
Page 26: ...22 User Guide Figure 19 Selecting an input channel ...
Page 36: ...Page intentionally left blank ...
Page 44: ...Page intentionally left blank ...
Page 56: ...52 User Guide ...
Page 62: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 107: ......