Technical data 89
NEMA ratings
Definitions
Sizing
Drive sizing is based on the rated motor current and power. To achieve the rated
motor power, the rated current of the drive must be more than or equal to the rated
motor current. Also, the rated power of the drive must be more than or equal to the
rated motor power. The power ratings are the same regardless of the supply voltage
in one voltage range.
Type
ACS380-04xx-
Input
rating
Input with
choke
Output ratings
Frame
size
Light-duty use
Heavy-duty use
I
1N
I
1N
I
Ld
P
Ld
I
Hd
P
Hd
A
A
A
hp
A
hp
3-phase
U
N
= 460 V (440…480 V)
01A8-4
2.6
1.6
1.6
0.75
1.1
0.50
R0
02A6-4
3.4
2.1
2.1
1.0
1.6
0.75
R1
03A3-4
4.8
3.0
3.0
1.5
2.1
1.0
R1
04A0-4
5.4
3.4
3.5
2.0
3.0
1.5
R1
05A6-4
7.7
4.8
4.8
2.0
3.4
2.0
R1
07A2-4
9.6
6.0
6.0
3.0
4.0
2.0
R1
09A4-4
12.2
7.6
7.6
5.0
4.8
3.0
R1
12A6-4
17.6
11.0
11.0
7.5
7.6
5.0
R2
17A0-4
22.4
14.0
14.0
10.0
11.0
7.5
R3
25A0-4
33.6
21.0
21.0
15.0
14.0
10.0
R3
032A-4
37.9
27.0
27.0
20.0
12.0
15.0
R4
038A-4
44.7
34.0
34.0
25.0
27.0
20.0
R4
045A-4
49.8
40.0
40.0
30.0
34.0
25.0
R4
050A-4
50.4
42.0
42.0
30.0
40.0
30.0
R4
3AXD10000299801.xls
U
N
Nominal supply voltage
I
1N
Nominal input current. Continuous rms input current (for dimensioning cables
and fuses).
I
max
Maximum output current. Available for two seconds at start.
I
N
Nominal output current. Maximum continuous rms output current allowed (no
overload).
P
N
Nominal power of the drive. Typical motor power (no overloading). The kilowatt
ratings apply to most IEC 4-pole motors. The horsepower ratings apply to most
NEMA 4-pole motors.
I
Ld
Maximum current with 110% overload, allowed for one minute every ten minutes
P
Ld
Typical motor power in light-duty use (110% overload)
I
Hd
Maximum current with 150% overload, allowed for one minute every ten minutes
P
Hd
Typical motor power in heavy-duty use (150% overload)
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...