134 Resistor braking
Selecting and routing the brake resistor cables
Use a shielded cable specified in section
Terminal data for the power cables
on page
.
Minimizing electromagnetic interference
Follow these rules in order to minimize electromagnetic interference caused by the
rapid current changes in the resistor cables:
• Install the cables away from other cable routes.
• Avoid long parallel runs with other cables. The minimum parallel cabling
separation distance should be 0.3 meters.
• Cross the other cables at right angles.
• Keep the cable as short as possible in order to minimize the radiated emissions
and stress on chopper IGBTs. The longer the cable the higher the radiated
emissions, inductive load and voltage peaks over the IGBT semiconductors of the
brake chopper.
Maximum cable length
The maximum length of the resistor cable(s) is 10 m (33 ft).
EMC compliance of the complete installation
ABB has not verified that the EMC requirements are fulfilled with external user-
defined brake resistors and cabling. The EMC compliance of the complete installation
must be considered by the customer.
Placing the brake resistor
Install the resistors outside the drive in a place where they will cool.
Arrange the cooling of the resistor in a way that:
• There is no danger of overheating to the resistor or nearby materials.
• The surrounding air temperature does not exceed the allowed maximum.
Supply the resistor with cooling air/water according to the resistor manufacturer’s
instructions.
WARNING!
The materials near the brake resistor must be non-flammable. The
surface temperature of the resistor is high. Air flowing from the resistor is of
hundreds of degrees Celsius. If the exhaust vents are connected to a ventilation
system, ensure that the material withstands high temperatures. Protect the resistor
against physical contact.
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...