62 Electrical installation
Measuring insulation
Drive
Do not do voltage tolerance or insulation resistance tests on the drive. The drive was
tested for insulation between the main circuit and the chassis at the factory. The drive
has voltage-limiting circuits which decrease the testing voltage automatically.
Input power cable
Before you connect the input power cable, measure its insulation according to the
local regulations.
Motor and motor cable
Measure the insulation of the motor and motor cable as follows:
1. Make sure that the motor cable is disconnected from the drive output terminals
T1/U, T2/V and T3/W.
2. Measure the insulation resistance
between the phase conductors and
between each phase conductor and the
protective earth conductor. Use a
measuring voltage of 1,000 V DC. The
insulation resistance of an ABB motor
must be more than 100 Mohm (reference
value at 25 °C or 77 °F). For the
insulation resistance of other motors,
refer to the manufacturer’s instructions.
Moisture in the motor casing decreases the insulation resistance. If you think that
there is moisture in the motor, dry the motor and measure again.
Brake resistor assembly
Measure the insulation of the brake resistor assembly as follows:
1. Make sure that the resistor cable is
connected to the resistor, and disconnected
from the drive output terminals R+ and R-.
2. At the drive, connect the R+ and R-
conductors of the resistor cable together.
Measure the insulation resistance between
the combined conductors and the PE
conductor with a measuring voltage of
1 kV DC. The insulation resistance must be
more than 1 Mohm.
ohm
M
3~
U1
V1
W1 PE
ohm
R-
R+
PE
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...