Electrical installation 71
Connection examples of two-wire and three-wire sensors
The figures give examples of connections for a two-wire or three-wire
sensor/transmitter that is supplied by the auxiliary voltage output of the drive.
Note:
Do not exceed the maximum capability of the auxiliary 24 V (200 mA) output.
Note:
The sensor is supplied through its current output and the drive feeds the supply
voltage (+24 V). The output signal must be 4…20 mA, not 0…20 mA.
AI2
Process actual value measurement or reference,
0(4)…20 mA,
R
in
= 137 ohm
AGND
+24V
Auxiliary voltage output, non-isolated,
+24 V DC, max. 200 mA
DGND
4…20 mA
Two-wire sensor/transmitter
+
-
P
I
AI2
Process actual value measurement or reference,
0(4)…20 mA,
R
in
= 137 ohm
AGND
+24V
Auxiliary voltage output, non-isolated,
+24 V DC, max. 200 mA
DGND
(0)4…20 mA
Three-wire sensor/transmitter
+
-
OUT
P
I
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...