174 BREL-01 relay output extension module
Start-up
To configure the operation of the relays added with the BREL module:
1. Power up the drive.
2. Set the parameter 15.01 Extension module type to 5 (BREL).
3. Use the control panel on the drive and set the parameters for relay outputs 2 to 5
in 15 I/O extension module. Refer to
ACS380 Firmware manual
(3AXD50000029275 [English]) for parameter descriptions.
Configuration parameters
The configuration parameters of the BREL module are in group 15 I/O extension
module.
No.
Name/Value
Description
Def/FbEq16/32
15 I/O extension module
15.01
Extension module
type
Sets the connected side-mounted extension module.
None
BREL
Basenut relay extension module
5
15.02
Detected extension
module
I/O extension module detected on the drive.
None
BREL
Basenut relay extension module
5
15.04
RO status
Status of the relay outputs.
1=1
Bit 0 RO2
Relay 2 output status. 1 = open / 0 = closed
Bit 1 RO3
Relay 3 output status. 1 = open / 0 = closed
Bit 2 RO4
Relay 4 output status. 1 = open / 0 = closed
Bit 3 RO5
Relay 5 output status. 1 = open / 0 = closed
15.05
RO force selection
Selection of relay outputs for forcing.
1=1
Bit 0 RO2
Relay 2 output status. 1 = selected to force / 0 = normal
Bit 1 RO3
Relay 3 output status. 1 = selected to force / 0 = normal
Bit 2 RO4
Relay 4 output status. 1 = selected to force / 0 = normal
Bit 3 RO5
Relay 5 output status. 1 = selected to force / 0 = normal
15.06
RO forced data
Relay output forcing.
1=1
Bit 0 RO2
Relay 2 output status. 1 = open / 0 = closed
Bit 1 RO3
Relay 3 output status. 1 = open / 0 = closed
Bit 2 RO4
Relay 4 output status. 1 = open / 0 = closed
Bit 3 RO5
Relay 5 output status. 1 = open / 0 = closed
15.07
RO2 source
Relay output 2 source selection.
Relay output 2 is open.
0
Relay output 2 is closed
1
For complete parameter list, refer to
ACS380 Firmware
manual
(3AXD50000029275 [English])
...
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...