90 Technical data
The ratings are valid at a surrounding air temperature of 50 °C (104 °F) for
I
N
. When
the temperature increases, derating is required.
The DriveSize dimensioning tool available from ABB is recommended for selecting
the drive, motor and gear combination.
Derating
The load capacity (
I
N
,
I
Ld
,
I
Hd
; note that
I
max
is not derated) decreases in certain
situations. In such situations, where full motor power is required, oversize the drive so
that the derated value provides sufficient capacity.
If several situations are present at a time, the effects of derating are cumulative.
Example:
If your application requires continuous 6.0 A of motor current (
I
N
) at 8 kHz switching
frequency, the supply voltage is 400 V and the drive is situated at 1500 m, calculate
the appropriate drive size requirement as follows:
(page
From the table, the minimum size required is
I
N
= 9.4 A.
):
The derating factor for 1500 m is 1 - 1/10 000 m · (1500 - 1000) m = 0.95.
The minimum size required becomes then
I
N
= 9.4 A / 0.95 = 9.9 A.
Referring to
I
N
in the ratings tables (starting from page
), drive type ACS380-04xx-
12A6-4 exceeds the
I
N
requirement of 9.9 A.
Surrounding air temperature derating, IP20
Frame size
Temperature
Derating
R0…R4
up to +50 °C
up to +122 °F
No derating.
R1…R3
+50
…
+60 °C
+122
…
+140 °F
Output current is decreased by 1% for every additional
1 °C (1.8 °F).
R4
+50…+60 °C
+122…+140 °F
Output current is decreased by 1% for every additional
1 °C on:
• ACS380-04xx-032A4-4
• ACS380-04xx-045A-4
Output current is decreased by 2% for every additional
1 °C on:
• ACS380-04xx-038A-4
• ACS380-04xx-050A-4
Summary of Contents for ACS380 Series
Page 1: ...ABB MACHINERY DRIVES ACS380 drives Hardware manual...
Page 4: ......
Page 12: ...12 Table of contents...
Page 20: ...20 Safety instructions...
Page 46: ...46 Mechanical installation...
Page 60: ...60 Planning the electrical installation...
Page 86: ...86 Maintenance...
Page 120: ...120 Technical data...
Page 122: ...122 Dimension drawings Frame R0 1 phase 230 V...
Page 123: ...Dimension drawings 123 Frame R0 400 V...
Page 124: ...124 Dimension drawings Frame R1 230 V...
Page 125: ...Dimension drawings 125 Frame R1 3 phase 230 V and 3 phase 400 V...
Page 126: ...126 Dimension drawings Frame R2 230 V...
Page 127: ...Dimension drawings 127 Frame R2 400 V...
Page 128: ...128 Dimension drawings Frame R3 400 V...
Page 129: ...Dimension drawings 129 Frame R4 400 V...
Page 130: ...130 Dimension drawings...
Page 138: ...138 Resistor braking...
Page 169: ...BTAC 02 pulse encoder interface module 169 Dimensions 3AXD50000031154 rev A...