Section 2 Installation
Power Supply
3BSE 027 941 R301
47
Safety Switch
A safety switch must be installed in the immediate vicinity of a controller
installation to allow for immediate total power supply disconnection to the
equipment, should the need arise. However, the prime function of the safety switch
is to provide a means of isolating the power supply completely during maintenance.
The safety switch must be installed in a location where it is both easily accessible
and clearly visible, i.e., outside any enclosure or cabinet.
Protective Ground
Always install a protective ground connection on equipment connected to a
230 V AC supply.
Fusing the External Mains Supply Cable
The recommended fuse rating for the external mains supply of a standard AC 800M
Controller configuration, housed within a floor or wall-mounted cabinet, is given in
Should the configuration be other than that stated, instructions for calculating
current consumptions can be found in the relevant I/O manual. For the
AC 800M Controller, see
Uninterruptable Power Supply
The SD82x series of power supply units comfortably handle the short power
interruptions (<20 ms) that y occur normally within an industrial environment.
Despite this, it is sometimes necessary to protect certain applications against brief
voltage failures by the installation of an Uninterruptable Power Supply (UPS)
device.
Table 5. External Mains Supply – Fuse Rating
Fuse Rating
Fuse Type
10 A
Slow to Rupture
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......