![ABB AC 800M Hardware And Operation Download Page 176](http://html1.mh-extra.com/html/abb/ac-800m/ac-800m_hardware-and-operation_3373854176.webp)
CI856 and TP856 – S100 I/O Interface
Appendix A Hardware Units
176
3BSE 027 941 R301
Technical Data
Table 50. CI856 S100 I/O Interface Specifications
Item
Value
Type
S100 I/O Communication Interface
Galvanic isolation
No
Status indicators
Run normally green, FAIL exceptionally red,
the indicator TO are yellow flashing at S100
I/O access time-outs.
Connector
36 pin centerline miniature ribbon
connector, female
Current consumption
(from CEX-bus 24 V DC)
120 mA typical (200 mA max.)
Power dissipation
2.9W typical
Capacity
Max 5 I/O racks with 20 I/O units each
Protection Rating
IP20 according to EN60529, IEC 529
Weight
700 g (1.5 lb) (package CI856K01 with
CI856 and TP856)
Dimensions
W 59 x H 185 x D 127.5 mm
(W 2.9 x H 7.3 x D 5.0 in)
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......