![ABB AC 800M Hardware And Operation Download Page 74](http://html1.mh-extra.com/html/abb/ac-800m/ac-800m_hardware-and-operation_3373854074.webp)
Installing the Ethernet Interface for MasterBus 300, CI855/TP853
Section 2 Installation
74
3BSE 027 941 R301
Installing the Ethernet Interface for MasterBus 300,
CI855/TP853
The CI855 is powered from the processor unit via the CEX-bus and requires
therefore no additional external power source.
The baseplate, TP853, provides two Ethernet ports for connection of redundant
Ethernet network for MasterBus 300.
Use the following procedure to install the CI855/TP853:
1.
Mount the unit on the DIN-rail, see
Mounting AC 800M Units onto DIN-Rail
Installing the PM8xx/TP830 Processor Unit in Single
2.
Connect the Ethernet twisted pair cable to the contact on the baseplate.
3.
Connect the other end of the Ethernet cable to a HUB.
Ethernet twisted pair Connection
The Ethernet twisted pair is connected via the 10 Base-T RJ45 connector located on
TP853. For a description of the connector, see
If the Ethernet cable has a transceiver, the connector from the transceiver must be
converted to RJ45. The communication unit, CI855, can not provide power to the
transceiver, therefore a separate power source must be used.
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......