Appendix A Hardware Units
CI851 and TP851 – PROFIBUS DP Interface
3BSE 027 941 R301
155
Indicators
Technical Data
Table 39. CI851 – PROFIBUS DP LED Indicators
Designation/Color
Function
F(ault) /Red
Unit error detected. Controlled by Control
Software. Set and cleared by the Hardware during
controller Reset.
R(un) /Green
Operating. Controlled by the Control Software.
Cleared by the Hardware during controller Reset.
Rx/Tx /Yellow
Transmission to or from the unit.
RTS /Yellow
Request to transmit from the unit.
Table 40. CI851 PROFIBUS DP Interface Specifications
Item
Value
Type
DP Master Class I
Protocol
PROFIBUS DP
Communication speed
9.6, 19.2, 93.75, 187.5, 500, 1500, 3000,
6000 or 12000 kbit/s
Galvanic isolation
Yes
Status indicators
Run normally green, Fault exceptionally
red, the two traffic indicators RTS and
Rx/Tx are yellow flashing controlled by the
traffic pace.
Connector
DB9, female
Current consumption
(from CEX-bus 24 V DC)
150 mA typical (200 mA max.)
Power dissipation
3.6W typical
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......