Mounting Dimensions for proper Ventilation
Section 2 Installation
90
3BSE 027 941 R301
Mounting Dimensions for proper Ventilation
To maintain adequate cooling airflow through the AC 800M Controller units, there
must be no obstruction within 50 mm (2 in) above and 25 mm (1 in) below the units,
as shown in
on page 90. Note that the CPU and Communication
Interfaces must be mounted on a horizontal DIN-rail.
Figure 26. Ventilation Requirements – Minimum Mounting Dimensions
>240 mm
(9.4 in)
>50 mm (2.0 in)
>50 mm (2.0 in)
>25 mm (1.0 in)
>25 mm (1.0 in)
Unobstructed areas
Unobstructed areas