![ABB AC 800M Hardware And Operation Download Page 146](http://html1.mh-extra.com/html/abb/ac-800m/ac-800m_hardware-and-operation_3373854146.webp)
Technical Data
Appendix A Hardware Units
146
3BSE 027 941 R301
Technical Data
For technical data on PM861 and TP830, see
Table 35. PM861 and TP830 – Technical data
Item
Value
Memory
•
2 MB flash PROM (firmware storage).
•
16 MB of SDRAM (11 MB available for application
program and 5 MB used for executable firmware).
Power Dissipation
6W typical
11W typical (incl. full supply to ModuleBus and CEX-bus,
see
Current Consumption
250 mA typical (430 mA max.)
(excl. supply of ModuleBus and CEX-bus, see
).
Power Input Connector
Four pin, screw connector L+, L–, SA and SB.
Power Supply
Requirements
Inputs designated L+ and L– 24 V nominal, variation
between 19.2 V DC and 30 V DC.
Redundant Power
Supply Status Inputs
Inputs designated SA, SB
•
Max input voltage 30 V
•
Min. input voltage for high level 15 V
•
Max input voltage for low level 8 V
These inputs are status inputs. The threshold levels are
logical "0" or "1" input limits, not power fail limits.
Power Reservoir
The processor unit has an internal 5ms power reservoir,
sufficient for the CPU to make a
controlled power down.
Protection Rating
IP20 according to EN60529, IEC 529.
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......