Current Consumption and Power Dissipation
Appendix B Power Consumption
204
3BSE 027 941 R301
Calculations
1.
Calculate the current requirements for each bus (ModuleBus and CEX-bus). Be
sure not to exceed the limits given in
on page 203. Data relating to
TB820, TB840 and CI830 is accessible from the S800 I/O documentation.
See
2.
Calculate the current consumption at 24V, for each electrical ModuleBus, by
adding::
I
m
= I
(24 V)
+ I
(5 V)
x 0.3
3.
To calculate the requirement for a specific power supply unit, total the results
of the 24V current consumption calculations, as follows:
I
tot
= I
m1
+ I
m2
+ .... + I
units
+ I
CI830s
+ I
TB820s
+ I
TB840s
If redundant CPUs are used, current for both CPUs must be included.
Summary of Contents for AC 800M
Page 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Page 2: ......
Page 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Page 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Page 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Page 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Page 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Page 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Page 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Page 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Page 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Page 228: ...QGH 228 3BSE 027 941 R301...
Page 229: ......