6.5. Analog outputs diagrams:
6.5.1. Current 0-20mA:
20mA
10mA
-20mA
-32768
0
16384
32767
6.5.2. Current 4-20mA:
20mA
12mA
-20mA
-32768
0
4mA
16384
32767
Voltage /- 10 V:
1 LSB = 10 / 2
11
= 4,88 mV
with minimum value ( step 8 )
V ( in volt ) = Value x (10 / 32767)
with value ( - 32767
≤
X
≤
+ 32767 )
Current output 0-20 mA:
1 LSB = 20.10
-3
/ 2
12
= 4,88 µA
with minimum value ( step 8 )
I ( in mA ) = Value x (20.10
-3
/ 32767)
with value ( 0
≤
X
≤
- 32767 )
Current output 4-20 mA:
Resolution is equal to 0-20 mA
I ( in mA ) = Value x (16 / 32767) + 4
with value (0
≤
X
≤
- 32767 )