Program Optimization
Page 6-14
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
5.3. Programming
Data exchange may be carried out directly through the inputs/outputs or by using function
blocks.
Exchange through inputs/outputs is particularly well adapted with a low number of data.
5.3.1. Bit transmission
Figure 6-9 : Bit transmission
The master central unit will receive the binary information from the slave central unit in the
Ixx.00 to Ixx+N.15 inputs, N+1 being the number of bits to transmit from the slave central unit
to the master slave unit modulo 16.
The slave unit will send the information through the O00.00 to ON.15 outputs.
The master central unit will send the binary information to the slave central unit through the
Oxx.00 to O(xx+M).15 outputs, (M+1) being the number of bits to transmit from the master
central unit to the slave central unit modulo 16.
The slave central unit will receive this information in the I00.00 to IM.15 inputs.
The N and M values may be different.
For example : The transmission of the "VALUE_M00" bit value from the slave 20 central unit to
the master central unit and the transmission of the "VALUE_FOR_SLAVE" bit value from the
master central unit to the slave 20 central unit.
CU master
CU slave
Address xx
CS 31 bus
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...